Installation instructions, only for experts

7. Testing

The following tests must be performed by a qualified electrician.
WARNING!
The following tests must be carried out with the power supply
switched on. There is a danger of electric shock.
● NEVER touch live parts.
1. Check the contact of the earth conductors on the earth conductor terminal.
2. When using a foil sensor (see Fig. 6: Connection area for sensor/control
unit/seat sensor on page 15)
a. Unplug the sensor. Error code 3
(see 9.1. Error messages on page 30) is displayed.
b. When the correct code is displayed, plug the sensor in again.
3. When using a safety temperature limiter (seeFig. 6: Connection area for
sensor/control unit/seat sensor on page 15)
a. Unplug the safety temperature limiter. Error code 2
(see 9.1. Error messages on page 30) is displayed.
b. When the correct code is displayed, plug the limiter in again.
4. When using infrared plates/infrared heaters
(see Fig. 7: Connection area for 230 V on page 16)
a. Check for functionality.