12
Device information for air-to-water heat pumps (heating only) LI 28TE
1
Type and order code
2
Design
2.1
Degree of protection according to EN 60 529 for compact devices
and heating components
2.2
Installation location
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
Air
3.2
Temperature spread of heating water
(flow/return flow)
3.3
Heat output / COP
3.4
Sound power level device / outdoors
3.5
Sound pressure level at a distance of 1 m (indoors)
3.6
Heating water flow with an internal pressure differential of m³/h / Pa
3.7
Air flow rate with an external static pressure differential of m³/h / Pa
3.8
Refrigerant; total filling weight
3.9
Lubricant; total filling weight
4
Dimensions, connections and weight
4.1
Device dimensions
4.2
Device connections to heating system
4.3
Air duct inlet and outlet (min. internal dimensions)
4.4
Weight of the transportable unit(s) incl. packing
5
Electrical Connection
5.1
Load voltage; Fuse protection
5.2
Control voltage; Fuse protection
5.3
Nominal power consumption
5.4
Starting current with soft starter
5.5
Nominal current
6
Complies with the European safety regulations
7
Additional model features
7.1
Defrosting
Type of defrosting
Defrosting tray included
7.2
Heating water in device protected against icing
7.3
Performance levels
7.4
Controller internal/external
1. This data indicates the size and capacity of the system according to EN 255 and EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters,
such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. These specifications can only be achieved with clean
heat exchangers. Information on maintenance, start-up and operation can be found in the respective sections of the installation and operating instructions. The specified values,
e.g. A2 / W55, have the following meaning: 2 °C external air temperature and 55 °C heating water flow temperature.
2. Operation with 1 compressors
3. Operation with 2 compressors
4. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35°C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
5. See CE declaration of conformity
6. The heat circulating pump and the heat pump controller must always be ready for operation.
EN-12
All manuals and user guides at all-guides.com
°C / °C
°C
at A7 / W35
K
1
at A-7 / W35
kW / ---
1
at A-7 / W45
kW / ---
1
at A2 / W35
kW / ---
1
at A7 / W35
kW / ---
1
at A7 / W45
kW / ---
1
at A10 / W35
kW / ---
dB(A)
4
dB(A)
m³/h / Pa
type / kg
type / litres
H x W x L cm
Inch
L x W cm
kg
1
A2 W35
kW
A
A2 W35 / cosϕ
A / ---
6
LI 28TE
IP 21
Indoors
Up to 58 / above 18
-25 to +35
9.9
2
9.9 / 2.4
3
19.1 / 2.8
2
3
2
12.8 / 3.1
3
22.3 / 3.2
2
14.2 / 3.2
3
25.8 / 3.5
2
3
2
14.7 / 3.3
3
29.1 / 3.7
62 / 68
58
2.3 / 3100
9000 / 0
8000 / 25
R404A / 4.0
Polyolester / 3.,8
171 x 75 x 103
G 1 1/4'' external
72.5 x 72.5
326
3~/PE 400 V (50 Hz) / C 25A
1~/N/PE 230 V (50 Hz) / C 13A
7.10
25
12.8 / 0.8
Automatic
Reverse cycle
Yes (heated)
Yes
Internal
5.0
9.4 / 2.4
17.4 / 2.7
8.4 / 2.0
16.7 / 2.2
12.4 / 3.0
20.8/ 3.1
13.9 / 3.2
25.0 / 3.4
12.8 / 2.7
24.5 / 2.9
14.3 / 3.2
28.2 / 3.6
4.9 / 13600
6.84
12.3 / 0.8
5
2

Publicité

loading

Ce manuel est également adapté pour:

Li 24teLi 28te