INVERT
FSAVE_TIME
FSAVE_TYPE
FSAVE-VAL-D
SIMULATE
ALARM_ENABLE
Operating instructions no. 801 148
Indicates wether the SP_D should be inverted before
writing to OUT_D in mode AUTO or RCas.
0 = not inverted
1 = inverted
Time in seconds from detection of a failure (Timeout
communication) beween Input and Output of the
Function Block before the OUT_D value is set to
FSAVE_VAL_D or in the FSAVE_TYPE defined value.
Defines reaction of the device, if communication fault is
still detected after FSAVE_TIME, if the DP-watchdog
expires or if a DP-clear-command is received. The
calculated ACTUAL MODE is MAN or AUTO
respectively (see table 4).
0 = freeze the last good state
1 = go to FSAVE_VAL_D
The present discrete output value to use when failure
occurs. Ignored if FSAVE_TYPE is freeze.
For commissioning and maintenance reasons, it is
possible to simulate the READBACK_D by defining the
value and the status. That means that the Transducer
Block and the DO-FB will be disconnected.
Switches the alarm evaluation of the sensors (not yet
included)
0 = short-circuit and idle on
1 = only idle on
2 = only short-circuit on
3 = Switched off
87