PROGRAMMING

NB:
The Multis switches to display
mode if no key is pressed after
a 25-second interval.
NB:
The Multis switches to display
mode if no key is pressed after
a 25-second interval.
SOCOMEC - Ref. : 875 513A
In programming mode use keys 6 and
4 (marked
and
) on the Multis.
All versions require that the CT ratios
be programmed before switching on.
PROGRAMMING CT RATIOS (MULTIS EP, MP, EG, MG)
KEYS
+
+
I MAX INTEGRATION PERIOD (MULTIS EG, MG)
KEYS
+
+
For the Mg and Eg versions, ensure
that the I Max is also programmed
before switching on.
INSTRUCTIONS
Press these two keys simultaneously
for 3 seconds; the display indicates
the T1 primary current rating (500A
default setting).
Press successively on this key
to scroll the rating values (choice
of ratings from 5 to 6000 A).
Press to pass to following pro-
gramme and enter CT ratio.
Press these keys simultaneously
for 3 seconds to accept value
and pass to U and I values display.
INSTRUCTIONS
To activate this function press
these two keys simultaneously
for 3 seconds if the Multis is not
in programming mode; otherwise,
proceed to the next step.
Displays integration period
(10 min. IM default setting)
Press successively on this key
to scroll different values (choice
of 5 to 30 min.).
Return to CT programming mode
and enter integration period.
Accept value, quit programming
and return to current / voltage
display (press for 3 seconds).