INSTALLATION
58
44
45
Modular version
SOCOMEC - Ref. : 875 513A
CLIMATIC ENVIRONMENT
For optimum operation this device
should be used within a temperature
range of -5° C up to 45° C with a
maximum relative humidity of 85 %.
SAFETY INSTRUCTIONS
To avoid damage to the device please
ensure the following points are res-
pected before connecting:
• enclosure indications,
• 50 or 60 Hz network,
CONNECTIONS TO THE NETWORK
Various connections are possible
according to the type of network.
For 3-wire networks the neutral
should not be connected. The Multis
modular version does not have an
auxiliary supply as it is self-supplied
by voltage inputs L1 and 2.
N
P1
L1
S1
P1
L2
S1
L3
S1 S2 S1 S2 S1 S2
1
3
5
7
2
4
6
8
N L 1 L 2 L 3
DIMENSIONS
105
85
• 230 or 400 V AC voltage ± 20 %
• 6A maximum current
• For the modular version, do not
connect the neutral point to the
inputs as these are not insulated.
The Multis panel-mounted version is
supplied by an auxiliary supply.
In this case, the neutral point can
be connected to the CTs' inputs as
these are insulated.