in the OFF position to avoid exposing the flowmeter electronics to the plant enviro
Guide condensé
Set jumpers during the commissioning stage to avoid exposing the electronics to t
environment.
Illustration 4-10 : Cavaliers d'alarme et de sécurité (sans option LCD)
Figure 3-19. Fieldbus Simulate Enable and Transmitter Security Jumpers
Simulate enable
The simulate enable jumper is used in conjunction with the Analog Input (AI) function blo
simulation. The jumper is also used as a lock-out feature for the AI function block. To ena
simulate enable feature, the jumper must transition from OFF to ON after power is applie
transmitter, preventing the transmitter from being accidentally left in simulator mode.
20
Débitmètre à effet vortex Rosemount
Août 2020
série 8800D