Endress+Hauser RMA 421 Mise En Service page 76

Transmetteur de process, ≥ software v1.10
Masquer les pouces Voir aussi pour RMA 421:

Publicité

Les langues disponibles

Les langues disponibles

Process transmitter
Process transmitter system messages
n
n
Display shows:
E 102
n
n
Display shows:
E 103
n
n
Display shows:
E 104
n
n
Display shows:
E 105
n
n
Display shows:
E 106
n
Flashes The 7 segment
display shows a
“TEXT”
74
The operating
parameters are
invalid or the
software version
does not correspond
with the saved
operating
parameters.
Possible cause is a
power down during
save sequence or a
software update.
The calibration
value of the
analogue input or
the rear panel
temperature
measurement are
faulty. Possible
cause is a power
down during
calibration, a not
calibrated unit or
hardware defect.
The calibration
value of the
analogue output is
faulty. Possible
cause is a power
down during
calibration, a not
calibrated unit or
hardware defect.
The analogue input
is defective.
Due to a setting up
fault an incorrect
scale setting was
made (lower and
upper values are
identical).
The unit is in
analogue output or
alarm relay
simulation mode.
E 102
All operating
parameters are reset
to factory default when
acknowledging using
the “E” push button.
Customer specific
settings made at the
factory are not
considered.
E 103
Please exchange the
unit.
E 104
Please exchange the
unit.
E 105
Please exchange the
unit.
E 106
Please correct the set
up values.
E 200
End simulation mode.