Process transmitter
5. Alarm set points/fault monitoring
The following addresses are only available if the unit is fitted
with the alarm relay option. One relay is allocated to each alarm
set point. On an alarm condition and fault, the allocated relay
switches to its idle position. A yellow LE fitted to the unit front
panel indicates the relay function in accordance with the NAM-
UR NE44 recommendation: LE illuminated on active relay;
LE off on idle relay. The option LC display gives further
information as to the type of limit infringement.
The following description is valid for the
alarm set points
arameter
* Operation mode
Selection of operation
mode of the alarm set
points and fault monitor
60
and
LIM1
LIM2
Setting up selections
MODE1 / MODE2
OFF
Set point and fault monitor
inactive
MIN
Minimum safety:
Event message on
undercutting the set point
and in fault condition
MAX
Maximum safety:
Event message on
exceeding the set point and
in fault condition
TRD
Trend monitoring:
Event message on
exceeding the preset signal
change per time unit set
point and in fault condition
ALARM
event message only in fault
condition, no set point
monitor
MIN-
Minimum safety:
event message when the
switch threshold is undercut
MAX-
Maximum safety:
event message when the
switch threshold is
exceeded
TRD-
trend analysis:
event message when the
preset set point of the signal
change per unit time is
undercut
LIM1 /
LIM2
Default
Actual
settings
setting
OFF