Commissioning; Balancer Or Differential Pressure Regulator - meibes LogoPack A Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

9. Commissioning

9.1 Balancer or differential pressure regulator

The balancer is used for hydraulic balancing, i.e. maintaining the necessary differential pressure for the hot water preparation in every
supply line of the heating system.
• Remove the protective cap (black).
• Adjust the spring setting by screwing the spindle in or out with a hexagon socket wrench (6 mm).
• Screw on the protective cap.
Technical data
Max. permissible operating pressure:
Max. permissible temperature:
Max. differential pressure over valve:
Differential pressure or control range:
Note:
The line must be filled so that the pressure in the flow line is not considerably higher than that of the return line, otherwise the balancer
valve will close.
0,50
0,45
0,40
0,35
0,30
0,25
0,20
0,15
0,10
0,05
0,00
10 bar (1000 kPa)
+120°C
2 – 4.5 bar (200 – 450 kPa), the greatest with low flow
0.1 - 0.4 bar (10 - 40 kPa)
Balancer G (DN 32)
0
200
400
600
800
1000
Flow rate to be maintained by balancer [l/h]
Setting curves
1200
1400
1600
1800
2000
2200
Spring setting
9
8
7
6
5
4
3
2
1,5
2400
2600
2800
3000
27