Temperature Sensor - Dimplex WI 120TU Instructions D'installation Et D'utilisation

Masquer les pouces Voir aussi pour WI 120TU:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English

7.4 Temperature sensor

The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature secondary circuit (R2) installed
(NTC-10)
Return temperature primary circuit (R24) installed (NTC-
10)
Flow temperature secondary circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
-20
-15
Temperature in °C
NTC-2 in k
14.6
11.4
NTC-10 in k
67.7
53.4
15
20
25
30
35
2.9
2.4
2.0
1.7
14.9
12.1
10.0
8.4
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig. 7.2 on page 6. The only exception is the outside
temperature sensor included in the scope of supply of the heat
pump (see Fig. 7.3 on page 6)
70
60
50
40
30
20
10
0
-20
-15
-10
-5
0
5
10
External temperature in [°C]
Fig. 7.2:Sensor characteristic curve NTC-10
20
18
16
14
12
10
8
6
4
2
0
-20
-15
-10
-5
0
5
10
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
EN-6
-10
-5
0
5
8,9
7.1
5.6
4.5
42.3
33.9
27.3
22.1
40
45
50
55
1.4
1.1
1.0
0.8
0.7
7.0
5.9
5.0
4.2
3.6
15
20
25
30
35
40
45
50
15
20
25
30
35
40
45
External temperature in [°C]
452237.66.68 · FD 0205
7.4.2 Mounting the outside temperature
sensor
The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the meas-
ured value is not falsified.
On the external wall of a heated room used as living space,
if possible on the north or north-west side of the building
Do not install in a "sheltered position" (e.g. in a wall niche or
under a balcony)
Not in the vicinity of windows, doors, exhaust air vents, ex-
ternal lighting or heat pumps
Not to be exposed to direct sunlight at any time of year
-
Dimensioning parameter sensor lead
10
Conductor material
3.7
Cable-length
18.0
Ambient temperature
60
0.6
Laying system
3.1
External diameter
7.4.3 Installing the strap-on sensor
It is only necessary to mount the strap-on sensors if they are in-
cluded in the scope of supply of the heat pump but have not yet
been installed.
The strap-on sensors can be fitted as pipe-mounted sensors or
installed in the immersion sleeve of the compact manifold.
Mounting as a pipe-mounted sensor
Remove paint, rust and scale from heating pipe.
Coat the cleaned surface with heat transfer compound (ap-
ply sparingly).
Attach the sensor with a hose clip (tighten firmly, as loose
sensors can cause malfunctions) and thermally insulate.
55
60
50
55
60
Cu
50 m
35 °C
B2 (DIN VDE 0298-4 /
IEC 60364-5-52)
4-8 mm
Hose clip
Strap-on sensor
Thermal insulation
www.glendimplex.de
WI 120TU

Publicité

Table des Matières
loading

Table des Matières