The electronic control unit Logica230 can be used to control 1 or 2 motors with a power not exceeding 300W+300W.
IMPORTANT: Should two motors be used, connect the limit switches of one single motor to the control unit.
a) The wire connections and the operating logic should be in compliance with regulations in force.
b) The cables featuring different voltage should be detached, or adequately insulated by an additional insulation of at least 1 mm.
c) The cables should be further fastened in proximity to the terminals.
d) Check all connections before powering the unit.
e) Check that setting of the Dip-Switches are the required ones.
f) Normally Closed inputs which are not in use should be short-circuited 230VAC – keep to phase/neutral).
Terminal No. Function
1-2
Power supply
3-4
Flashing light
4-5
Light, Motor
6-7-8
Motor 1/2
9
COM
10
SWO
11
SWC
12
STOP
13
PHOT
14
OPEN
15
CLOSE
16
Step-by-Step
17-18
24 Vac
19-20
SCA
21-22
COSTA
23-24
Aerial
CM-CM
Capacitor
0-12-12
Secondary
L1-N1-T
Primary
J3
Radio receiver
The courtesy light stays on for about 90s at each operation.
The safety EDGE should be connected only to the special inputs. Two types of EDGE can be used:
If a safety edge is used with 8K2 resistance, the "DAS" jumper should be closed.
If a mechanical safety edge with N.C. contact is used, the "DAS" Jumper should be opened.
If no edge is used, terminals 21-22 should be short-circuited.
1) Power the control unit
2) Manually release the system and completely open the door.
3) Adjust the opening limit switch cam, the SWO LED turns off.
If braking is required in the opening phase, the limit switch triggering should be anticipated.
4) Shut the door completely.
Logica230 Control unit
GENERAL WARNINGS
INPUT/OUTPUT FUNCTIONS
Logica230 Control Unit
Description
Input, 230VAC 50Hz (1-Phase/2-Neutral)
Connection of flashing light, 230Vac 40W max.
Connection to the courtesy light
Connection to motor 1/2 : (6-speed/7-Com/8-speed)
Should 2 motors be used, connect the second motor in parallel.
Common for limit switch and all control inputs.
Input, OPEN limit switch (N.C. contact)
Input, CLOSE limit switch (N.C. contact)
Input, STOP push button (N.C. contact)
Input, connection to safety devices, N.C. contact
(e.g. Photocells)
Input, OPEN push button (N.O. contact)
Input, CLOSE push button (N.O. contact)
Input, step-by-step push button (N.O. contact)
Output, power supply of accessories, 24Vac/1A max.
Free contact, N.O. for open door warning light.
Input, safety edge contact
Resistive edge: Closed "DAS" jumper
Mechanical edge: Open "DAS" jumper
If the safety edge is activated in the opening phase, the gate stops.
In the closing phase, the gate stops and the performs a movement reversion (opens) for
3s.
Connection to the radio receiver card of the aerial (23-screen/24-signal).
Connection, capacitor
Connection, winding of secondary transformer
Connection, winding of primary transformer
Connector for radio receiver.
The RI versions have a built-in radio receiver
REMARKS:
TO ADJUST THE LIMIT SWITCHES