E SAFETY NOTES
For your own safety, read all instructions and mounting steps carefully.
Keep the instructions for maintenance or disassembly work.
The electrical connection must be carried out by professional personnel trained
and authorised for this purpose.
WARNING - risk of electric shock!
• Never work on the luminaire with voltage applied.
The light source of this luminaire shall only be replaced by the manufacturer or
a service technician authorised by the manufacturer or a comparably qualified
person.
WARNING - risk of electric shock!
• If the light source malfunctions or fails, please contact TRILUX.
• LED-Modul Risikogruppe 1
D
• The surface temperatures of the luminaire are limited.
The luminaire is suitable for use in areas where the deposition of conductive dust
is expected.
Intended use
• The continuous line 765...IP64 consists of:
Suspension accessories
Trunking / cover
End caps / coupling seal
t a
Gear tray
• The continuous line 765...IP64 is intended for indoor use. The permissible
ambient temperature t a depends on the gear trays used.
• Suitable for mains through-wiring. Max. total current 16 A at 2.5 .
• Not suitable for corrosive atmospheres (e.g. swimming pools, intensive animal
husbandry, tunnels)
• Protection rating: IP64
• Safety class: I
Important information on electronic control gear units (ECG)
• A neutral conductor interruption in the three-phase circuit leads to overvoltage damage
in the lighting system. Only open the neutral conductor isolating terminal in de-energized
state, and close the neutral conductor isolating terminal before switching on again.
• Do not exceed the maximum permissible ambient temperature ta of the luminaire. Excee-
ding this limit reduces the service life and in extreme cases there is a risk of premature
failure of the luminaire.
• Lay out the connection cables for the control inputs of dimmable ECGs (1-10 V, DALI etc.)
230 V mains voltage-proof (basic insulation).
04
/ 56
E LINE NEXT FIX LED
07650...IP64 / 07650 TA...IP64
07650 KS IP64 / 07650 KD IP64
7651...
10186010 / XI 21 / ©trilux.com
E LINE NEXT FIX LED
Avoidance of cutting injuries
• Install the luminaire components using protective gloves.
Avoidance of contamination
• Wear clean installation gloves.
Directive 2014/53/EU
Simplified EU Declaration of Conformity according to the RED Directive if the
luminaire is equipped with a control gear unit with NFC interface or a radio compo-
nent: TRILUX hereby declares that the radio system type in the following luminaire
types complies with Directive 2014/53/EU: 765...
The full text of the EU Declaration of Conformity is available on the internet at:
www.trilux.com/eu-conformity
Disposal of waste electrical and electronic equipment
• Always collect and dispose of old electrical and electronic equipment separately
at the end of its service life. In case of doubt, seek information about environ-
mentally-compliant waste disposal from your local district authority or special
waste disposal companies.
• For important information on the energy efficiency of TRILUX luminaires and on
maintaining and disposing of luminaires, see the Internet at:
www.trilux.com/ec245
Page 29 - 31
Electrical connection
Page 18 - 27
Suspension accessories
End cap
Page 28 + 34
Cover 07650 TA...IP64
Page 50 - 52
10186010 / XI 21 / ©trilux.com
Page 20 - 35
Trunking 07650...IP64
Page 35 - 49
Gear tray 7651...
05