1.
Adjustment of the decimal place (see Input Signal and
Measurement Range) according to 4.2.1.
2.
Adjustment of the measurement range in 0 and in FS
Select either M3 or M4 with the + / - keys and activate
the parameter selection
with SET . Then enter the beginning and end values with
the + / - keys and save with the SET key. Pressing the
SET key ends the procedure.
3.
Saving the configuration
The parameter configuration is ended as soon as the
value for in FS is entered with SET . The saving of this
configuration ensues with End . Another entry with SET
saves the parameter configuration. The instrument
automatically switches into the operating mode
Measuring and Display .