Parameter configuration of the SCE-020-03 with
SCFT-xxx-11-07
1.
Set the decimal place (watch the k-factor) according to
Section 4.2.1.
2.
Setting of the k-factor according to the turbine type label.
Select M3 with the + / - keys and activate the parameter
selection with SET . Then set the k-factor with the + / -
keys and confirm with SET . The setting is ended with
SET .
3.
Setting iPr = 0
Select M4 with the + / - keys and activate the parameter
selection with SET . Then enter iPr = 0 over the + / - keys
and confirm with SET . The setting is ended with SET .
4.
Saving the configuration
The parameter configuration is ended as soon as the iPr
value is confirmed with SET . This configuration is saved
with End . A further confirmation with End saves the
parameter configuration. The instrument switches
automatically into the operating mode Measuring and
Display .