Diagnostics - Nidec Leroy-Somer Field Keypad RTC Manuel D'installation

Masquer les pouces Voir aussi pour Leroy-Somer Field Keypad RTC:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Keypad screen
Parameter mm.000
CodeSys transfer
_
File
> Drive
Are you sure?
Parameter mm.000
CodeSys transfer
_
File
> Drive
Wr sx mxx pxxx
Parameter mm.000
CodeSys transfer
_
File
> Drive
Success

4.3 - Diagnostics

Cloning function trips are detailed in the table below.
For more information about other drive trips, please refer to the installation and quick commis-
sioning manual ref. 5511 (www.commanderID300.info).
Trip code
Err Data 64bit
Err Drv Timeout
Err Product ID
Unsupported Drv
«Err Kypd Timeout»
Err Kypd No File
Err Kypd File Op
Err Kypd File Rd
Err Kypd File Wr
Err Kypd File Cl
Err Drv Parm Wr
Err Drv Parm Rd
Err Drv File Opn
Err Drv Xfer Crc
Err Drv Xfer Siz
Err Drv File Rd
Err Drv File Wr
Err Drv File Cls
Installation and connections
5690 en - 2020.03 / c
Field RTC Keypad
Action
Comments
Confirm the storing
Downloading the program
-
Download successfully completed
-
Description
Uploading 64 bit parameter is not supported
Drive communication timed out
Mismatch drive and parameter file
Drive is not in the supported list
Keypad flash file access timed out
No parameter files for downloading available
Opening flash file error occurred
Reading flash file error occurred
Writing flash file error occurred
Closing flash file error occurred
Parameter write error occurred
Parameter read error occurred
Error opening drive CoDeSys file
Invalid CRC after transferring drive CoDeSys file
Invalid size after transferring drive CoDeSys file
Reading drive file error occurred
Writing flash file error occurred
Closing drive file error occurred