4.2
Power terminals
Fig. 4−1
Plug connectors for power terminals
{
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
EDKCSEX064 DE/EN/FR 4.0
Death or severe injuries when the device is touched in the event
of a fault.
Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter ³ 10 mm
l
Electrical installation
Power terminals
2
or PE conductor must be connected twice)
4
ECSXA080
97