CARATTERISTICHE TECNICHE
Auxiliary power supply
Rated battery voltage
Maximum current consumption
Max power consumption/dissipation
Fuse
Voltage range
Minimum voltage during the starting
Cranking dropout
Negative digital inputs (1.1, 1.2, 1.3, 1.4 and 1.5 terminals)
Type of input
Current input
"Input low" voltage
"Input high" voltage
Input delay
Positive digital input (1.6 terminal)
Type of input
Current input
"Input high" voltage
"Input low" voltage
Input delay
Speed input "W"
Type of input
Voltage range
Frequency range
Engine running input (500rpm) for permanent magnet alternator
Voltage range
Engine running input (500rpm) for pre-excited alternator
Voltage range
Maximum input current
Maximum voltage at +D terminal
Pre-excitation current ( 3.5 terminal)
Voltage generator input
Maximum rated voltage Ue
Measuring range
Frequency range
Measuring method
Measuring input impedance
Wiring mode
Current input
Rated current Ie
Measuring range
UL rating
Measuring method
Overload capacity
Overload peak
Power consumption
12 or 24V
indifferently
165mA at 12V
and 105mA at 24V
2W a 12V
and 2,5W at 24V
800mAT (time-delay)
9...35V
6.7V
0V for 200ms
Negative
≤10mA
≤1.5V (typical 2.9V)
≥5.3V (typical 4.3V)
≥50ms
Positive
4mA 12V
- 8mA 24V
≥5.3V (typical 4.3V)
≤1.5V (typical 2.9V)
≥50ms
AC coupling
5...50Vpp
40...2000Hz
~
0...40V
0...40V
12mA
12 or 24V
(battery voltage)
170mA 12V
- 130mA 24V
~
~
415V
L-L (240V
L-N)
~
50...500V L-L (290V
L-N)
45...65Hz
True RMS
>3.3M≤Ω
3PH
L1-L2-L3
2PH
L1-L2-N
1PH
L1-N
5A
0.02...6A
Supplied by an external current transformer
(low voltage). Max. 5A
True RMS
+20% Ie
50A for 1 second
<0.3VA
Measuring accuracy
Generator voltage
Static outputs (— battery voltage outputs)
Type of output
Rated current
Protections
Relay output 6.1-6.2-6.3 terminals (voltage free)
Type of contact
UL Rating
Rated voltage
Rated current at 250VAC
Communication lines
TTL/RS232 Serial interface
Insulation voltage
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Power frequency withstand voltage
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum pollution degree
Overvoltage category
Measurement category
Altitude
Connections
Type of terminals
Conductor cross section (min... max)
UL Rating
Conductor cross section (min... max)
Tightening torque
Housing
Version
Material
Degree of protection
Weight
Certifications and compliance
Certifications
Comply with standards
±0.25% f.s. ±1digit
Negative
1.2A
Short circuit and Overload
1 changeover
B300
30V
1A Pilot Duty
~
~
250V
rated (400V
max)
8A AC1 (1.5A AC15)
Fixed baud-rate 38400 bps
Connection to PC by 51C11 cable
~
415V
6kV
4kV
-30...+60°C
-30...+80°C
≤90%
3
3
III
≤2000m
Plug-in / removable
2
0.2...2.5 mm
(24...12 AWG)
2
0,75...2.5 mm
(18...12 AWG)
0.5 Nm (4.5 lbin)
Flush mount
Self extinguishing UL94 V-0 black Noryl
IP54 on front
IP20 terminals
400g
cULus (pending)
IEC/EN 61010-1, IEC/EN 61000-6-2,
IEC/EN 61000-6-3, IEC/EN 61000-4-3,
IEC/EN 60068-2-27, IEC/EN 60068-2-6
(LROS-Lloyd's Register Of Shipping),
IEC/EN 60068-2-61 (RINA-Italian Naval
Register), UL 508 and CSA C22.2_N°14-95
(cULus).
17