5.3
Mounting the product
Verify that the product is mounted to an even, rigid and dry wall at eye
level.
Verify that the product is accessible and easy to oversee at all times.
Verify that the product is protected against water and splash water.
Verify that the product is not mounted in a humid room.
Verify that the ambient temperature is not exceeded at the product.
Verify that the product is not installed in hazardous areas or in manholes
of underground tanks.
Verify that the product is mounted in a protective housing with degree of
protection IP 55 in the case of outdoor installation. If the product is
installed in a protective housing, an additional weather-proof audible
alarm must be installed outside of the protective housing.
Verify that the product is not exposed to direct sunlight.
If the leak detector is installed below rooftops or in rooms that are only
partially closed, verify that the product is protected against direct atmos-
pheric influences or use a protective housing as mentioned above.
Mounting
Eurovac HV
EN
20