Télécharger Imprimer la page

afriso Eurovac HV Manuel D'utilisation page 77

Masquer les pouces Voir aussi pour Eurovac HV:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5.3
Mounting the product
 Verify that the product is mounted to an even, rigid and dry wall at eye
level.
 Verify that the product is accessible and easy to oversee at all times.
 Verify that the product is protected against water and splash water.
 Verify that the product is not mounted in a humid room.
 Verify that the ambient temperature is not exceeded at the product.
 Verify that the product is not installed in hazardous areas or in manholes
of underground tanks.
 Verify that the product is mounted in a protective housing with degree of
protection IP 55 in the case of outdoor installation. If the product is
installed in a protective housing, an additional weather-proof audible
alarm must be installed outside of the protective housing.
 Verify that the product is not exposed to direct sunlight.
 If the leak detector is installed below rooftops or in rooms that are only
partially closed, verify that the product is protected against direct atmos-
pheric influences or use a protective housing as mentioned above.
Mounting
Eurovac HV
EN
20

Publicité

loading