5.4.1
Power supply
Connect the product to mains by means of a permanently installed cable,
for example NYM-J 2 x 1.5 mm
1. Route the mains cable through the upper or bottom cable gland into the
product.
2. Connect the phase to terminal L1 and the neutral conductor to
terminal N.
3. The supply cable to the product must have a separate fuse, maximum
16 A.
5.4.2
Output
DAMAGE TO THE PRODUCT
Destruction of the switching contact and adverse effects on the function of elec-
trical systems due to voltage peaks when inductive consumers are switched off.
•
Use commercially available standard RC combinations such as 0.1 µF/
100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.
The output signal of the leak detector is made available via a voltage-free
relay contact (1 changeover contact).
1. Permanently install the relay cable.
2. Route the relay cable through the upper or bottom cable gland into the
product and connect it to the terminals with the corresponding designa-
tions.
3. Verify safe separation of the relay cable.
- The insulation characteristics of the relay cable must at least comply
with IEC 60227 or IEC 60245.
If no error condition is present, the relay is de-energised; in case of an
alarm, the relay is energised.
Mounting
2
.
NOTICE
Eurovac HV
EN
26