2.2
Intended use
The product is a leak detector for vacuum systems as per EN 13160-1,
class I (EN 13160-2).
This product may only be used to detect leaks in tanks which are not pres-
surised (i.e. operated under atmospheric conditions) and which are used for
the aboveground or underground storage of liquids.
Tanks
•
Double-walled steel tanks as per EN 12285-1/-2, DIN 6618-2/-4, DIN
6619-2, DIN 6623-2, DIN 6624-2, DIN 6608, DIN 6616, DIN 6625
•
Steel or plastic tanks, double-walled or single-walled with leak protection
lining or leak protection coating, with suitable interstitial space as per
EN 13160-7.
The interstitial spaces of the tanks must be resistant to the liquid and its
vapours and must not contain leak detection fluid.
Liquids
• Water-polluting liquids with a flash point > +55 °C, which do not become
viscous and which do not release solid matter
•
AdBlue® (urea solution 32.5 %) as per DIN 70070
The product must be resistant to the liquid and its vapours. The materials
used are: PVC, silicone, ABS, NBR, PA6, EPP, EPDM. Resistance has been
proven for the liquids listed in the list of substances in chapter "List of sub-
stances".
The permissible density of the liquid depends on the tank used and its con-
tent.
Information on safety
Eurovac HV
EN
4