4.
INSTRUCTIONS FOR USE
FEKAFOS is a preassembled system, ready for installation, requiring no adjustment; it is ideal for the collection
and disposal of sewage and domestic waste water from cellars, situated below the level of the sewer network. In
compliance with the accident-prevention regulations in force, the FEKAFOS cannot be used for conveying
inflammable or explosive liquids, such as petrol, diesel fuel, fuel oil, solvents, etc.
5.
INSTALLATION
Do not lift, carry or operate the pumps holding them hanging by their power cable.
5.1
5.2
An example of installation is shown on page 26.
The tank may be laid on the floor, under the ground or housed in a masonry pit.
5.3
In any case the surface on which it is laid must be perfectly horizontal and it must be ensured that
the whole bottom of the tank is in contact with the surface.
The tank cover can bear foot traffic (max. weight 100 Kg).
5.3.1 In indoor installations (garage, basement, technical room), the tank must be fixed to the ground using the
slots provided, as indicated in the figure.
FIX THE TANK TO THE GROUND
BEFORE USE
Ensure that the difference in level between the pump and the sewage network is
compatible with the pump performance.
5.4
Pump assembly procedure
5.4.1 200 l tanks:
For the parts references, see the diagram on page 23.
1. Remove the cover of the tank, slackening the retaining screw on the metal strap and removing the
straps around the cover.
2. Lay the pump on the bottom in the place provided (see Fig.A page 23).
3. Connect the pump to the delivery hose. For FEKA 600 use the coupling (118b-118c).
Check that the clamps of the delivery hose are correctly fixed.
5.4.2 280 l – 280 l DOUBLE - 550 l tanks:
For the parts references, see the diagram on page 24-25.
For 550 l – 280 l DOUBLE tanks perform the following operations for both pumps.
1.
Remove the cover of the tank, slackening the retaining screw on the metal strap and removing the
straps around the cover.
2.
Remove the top screw from the flange on the delivery side (268).
3.
Assemble the anti-rotation bracket (316).
4.
Replace the screw (268).
5.
Extract the slide from the coupling foot and connect it to the delivery port of the pump. Using the
screw 267a (for Feka ref.260b) and the nut 397c, fix the slide to the pump as indicated in the figure
(see page 25).
6.
Reposition the slide/pump assembly on the foot (5).
ENGLISH
268
397c
316
260a
FEKA VS - VX
29
260b
126a
FEKA 2500