Télécharger Imprimer la page

PNI SafeHouse HS650 Manuel Utilisateur page 8

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 117
English
SIM slot
SOS button lights
Lighting
The LED flashes alternately
The LED pulses
The LED is constantly lit.
Connecting wired accessories
Zone 1, Zone 2, Zone 3 and Zone 4 are the EOLR wired zones that support
devices (sensors) with NO (open circuit) and NC (closed circuit) signal with
a response time of 300 ms. Maximum resistance of the area: 11000 Ohms +
EOLR
Connect the NC (Normally Closed) devices in series at the top of the loop. The
EOLR resistor must be connected in series with the devices to the last device.
Connect the NO (open circuit) devices in parallel, in the loop.
On/Off
5V USB
Wired zones connection
Meaning
The system is in alarm state
The system is armed
The system is disarmed
8
8
Wired siren connection
Microphone

Publicité

loading