Manual INERIS 17 ATEX 9002U
Characteristics :
4.4.
Head IP IEC60529
Type
Metalic
Plastic
Signaling
XLW4BV... XLW5AV...
units XLW
Signaling
XAW5AV...
units XAW5
Siganling
ZAW5AV...
head units
Illuminated
pushbut-
XLW5BP...
tons
Illuminated
push-push-
XLW4BH...
buttons
Service temperature of non-metallic parts and IP rating
Signaling units XLW...:
Signaling units XAW5...:
Signaling head ZAW5...:
Pilot light ZBWV/L...:
Contact blocks
ZBWE10... or 11...:
Service life
Contact blocks
ZBWE10 / 11...:
Pilot light ZBWV/L...:
Storage temperature:
Wiring
by screw clamp 2x1,5 mm² or 1x2.5 mm²
with tip: orque: 0,8 Nm à 1,2 Nm max.
5.
Safety instructions
The following safety instructions should be read
in conjunction with the following standards:
−
IEC 60079-14 (Electrical installations
design, selection and erection)
−
standard IEC 60079-17 (Electrical installa-
tions inspection and maintenance)
−
standard IEC 60079-31 (Equipment dust
ignition protection by enclosure "t").
−
decrees, laws, directives, circulars of appli-
cation, standards, rules of art and any oth-
Edition March 2017
Copyright
Contact block
Pilot light
ZBWE...
ZBW...
ZBW...B
Ue = 6 à
Ue = 24 à
24 V
254 V
Ie =
Ie = 10mA
21mA
max
max
Ue = 6 à 415V
Ie = 10A max
IP65
-20°C < T°< +75°C
(* page 5)
-40°C < T°< +60°C IP66
-50°C < T°< +75°C
-50°C < T°< +75°C
-50°C < T°< +75°C
1 000 000 operating
cycles for contacts
100 000 hours
-50°C ... +70°C
thuba Ltd., CH-4015 Basel
Switzerland