8.9 Connection plan

T1 Temperature sensor
Outside air

8.10 Brine circulation pump

Three sizes of pump are recommended, in
order to guarantee that there is sufficient
brine mass flow. Please refer to the table
shown here for determining the suitable pump
and pump stage.
The Wilo ST 15/6 circulation pump that we
selected delivers this brine mass flow, e.g. for
a room air system with a volumetric flow of
250 m³/h, from a setting of "Speed level II" or
higher.
42
T2 Temperature sensor outside air
Air
Ground
Re-
volu-
extrac-
quired
metric
tion
brine
flow
rating
volu-
(V)
(Q)
metric
flow
[m³/h]
[W]
[l/h]
100
533
178
150
800
267
200
1067
356
250
1333
444
300
1600
533
350
1867
622
400
2133
711
Pump level
to be set
UPS
UPS
UPS
25-40
25-60
25-80 or
or
or
Wilo
Wilo
Wilo
ST 15/8
ST 15/4
ST 15/6
I
I
I
I
I
I
II
I
I
II
I
III
I
II
III