● If operating with Tmf, it is necessary to remove the connection jumper between terminals 1 and 4 of MR.
● When operating with CONTINUOUS MODULATION using a LANDIS RWF 40 regulator, remove the
connection jumper between terminal 5 of MPE and terminal 9 of MR.
N.B. The connection from probe S to terminal G of MRM is required only with the pressure probe (LANDIS QBE...).
ATTENTION: Do not invert the neutral with the phase - Perform a good earth connection - Must be workmanlike
performed and comply with the regulations in force.
ELECTRODES ADJUSTMENT
There are two ignition electrodes and a control electrode. They must never touch the diffuser or other metallic
parts. If this were to happen they would no longer work , thus impairing operation of the burner itself.
The position of the electrodes should be checked after any work on the combustion head.
GAS CONNECTION
The system must be equipped with all the accessories required by current regulations; avoid exercising excessive
force on components.
Remember also the necessary free space required for the burner and the boiler maintenance.