ELECTRODES POSITION
All burners have two starting electrodes and one control electrode.
To position the electrodes refer to the figure at side and observe the values in the table below.
3 ÷ 4 mm
Control electrode
10 mm
N.B. The starting electrodes and control electrode should never touch the deflector or the draught tube; if so,
their function will be voided and burner operation will be compromised.
GAS CONNECTION
The system must be complete with the accessories prescribed by regulations. Do not exert mechanical force on
components.
Also take into account the spaces required for burner and boiler maintenance.