The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
The second test is completed.
Write down the pressure and/or flow rate, and state which test
gave the highest pump performance:
•
First test
•
Second test
•
Make new test.
The correct direction of rotation has now been set.
•
Press OK to set the setpoint. See Setpoint (15/16) on page 23.
10.4 Menu GENERAL
If the start-up guide is started, all previous
Note
settings will be erased!
The start-up guide must be carried out on a cold
motor!
Note
Repeating the start-up guide may lead to a
heating of the motor.
The menu makes it possible to return to the start-up guide, which
is usually only used during the first start-up of the CUE.
10.4.1 Return to start-up guide (0.1)
State your choice:
•
Yes
•
No.
If Yes is selected, all settings will be erased, and the entire start-
up guide must be completed.
10.4.2 Type code change (0.2)
This display is for service use only.
10.4.3 Copy of settings
It is possible to copy the settings of a CUE and reuse them in
another one.
Options:
•
No copy.
•
to CUE (copies the settings of the CUE).
•
to control panel (copies the settings to another CUE).
The CUE units must have the same firmware version. See section
10.6.16 Firmware version (2.16).
25