Burkert 0121 Manuel D'utilisation page 12

Masquer les pouces Voir aussi pour 0121:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Check▶electrical▶continuity▶between▶coil▶and▶body▶(protective▶con-
ductor▶function).
4
2
3
1
Fig. 4:
Electrical connection pulse variant (CF 02)
note!
▶ ▶ Prevent▶simultaneous▶pulsing▶on▶both▶coil▶windings.
▶ ▶ Parallel▶to▶the▶terminals,▶no▶other▶consumers▶(relay,▶etc.)▶may▶be▶
connected.
▶ ▶ The▶respective▶coil▶connection▶that▶does▶not▶carry▶current▶must▶be▶
galvanically▶isolated▶(open).
▶ ▶ In▶case▶two▶or▶more▶valves▶are▶connected▶in▶parallel,▶the▶use▶of▶two-
pole▶or▶multi-pole▶switches▶must▶ensure▶that▶this▶requirement▶is▶met.
12
Terminal▶1
(
=)▶
Terminal▶2
(+)▶L1
Terminal▶3
(–)▶N
Protective▶
PE
conductor
english
7.3 Kick-and-drop-electronic variant
(solenoid coil acp016)
Information▶on▶the▶solenoid▶coil▶Type▶ACP016▶can▶be▶found▶in▶the▶
corresponding▶operating▶manual▶at▶www.burkert.com.
Danger
If solenoid coils feature a terminal box, also observe the
following:
▶ ▶ Insert▶permanently▶installed▶cables▶and▶lines▶only.
▶ ▶ Use▶a▶suitable▶cable▶and▶line▶entry.▶Observe▶specifications▶in▶the▶
operating▶instructions▶ACP016.
▶ ▶ The▶terminals▶in▶the▶terminal▶box▶are▶intended▶for▶wires▶between▶
0.5▶mm
▶and▶2.5▶mm
.
2
2
▶ ▶ Tighten▶terminal▶screws▶to▶0.25▶Nm.
▶ ▶ Lock▶housing▶cover▶properly.▶Tighten▶lock▶screw▶to▶2▶Nm.
▶ ▶ Check▶continuity▶of▶the▶protective▶conductor▶connection.
▶ ▶ Before▶opening▶the▶housing▶cover,▶disconnect▶the▶power▶supply.
▶ ▶ Connect▶maximum▶two▶conductors▶to▶each▶terminal.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

033003310124012503320333

Table des Matières