BURNER ADJUSTMENT TABLE
NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the instal-
lation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in
this manual.
Actual firing
rate 5% ±
US GPH
0.50
0.60
0.75
0.80
0.95
Actual firing
rate 5% ±
US GPH
0.75
0.85
1.00
1.10
1.25
1.50
1.65
The above set up charts are a starting point only.
The burner and appliance must be properly set up using proper combustion testing equipment.
Any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input is cor-
WARNING
responding the correct BTU/hr or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropri-
ate installation codes (e.g. CSA B139 or NFPA #31).
BURNER START-UP CYCLE
Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
MODEL F3 BURNER
Nozzle
size
GPH
.40 x 60º/80º
.50 x 60º/80º
.60 x 60º/80º
.65 x 60º/80º
.75 x 60º/80º
MODEL F5 BURNER
Nozzle
size
GPH
.60 x 60/ 80º
.65 x 60/ 80º
.85 x 60/ 80º
1.00 X 60/ 80°
1.10 x 60/ 80º
1.25 x 60/ 80º
1.35 X 60/ 80°
~ 12s
Pump
pressure
PSI
bar
160
11.0
150
10.4
150
10.4
150
10.4
160
11.0
Pump
pressure
PSI
bar
145
10
145
10
145
10
145
10
145
10
145
10
145
10
Lock-out, due to light-failure
~ 12s
12
Turbulator
Air damper
setting
setting
0.0
0.5
1.5
2.0
3.0
Turbulator
Air damper
setting
setting
0.0
0.5
1.0
2.0
2.5
3.0
4.0
~ 5s
2.3
2.7
3.4
3.6
4.3
2.25
2.5
2.75
3.0
3.5
4.25
6.0
D5229
2903222