GB
A) Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the flat side, ensuring the bolt heads
are flush with the flat surface. Secure in place using two special CHROME NUTS (2) provided.
B) Position the MOUNTING GASKET (3) between the flat surface of the UNIVERSAL MOUNTING FLANGE (10) and
the appliance. Line up the holes in the UNIVERSAL MOUNTING FLANGE with the STUDS (4) on the appliance
mounting plate and securely bolt the UNIVERSAL MOUNTING FLANGE to the plate.
C) Secure the two semi-flanges of the ADJUSTABLE COLLAR (9) to the AIR TUBE using the two long BOLTS (6). Be
sure that the ADJUSTABLE COLLAR (9) is properly positioned so the outside edge of the END CONE will be at least
1/4" inch (6.5 mm) back from the inside wall of the refractory of the combustion chamber (see dimension B above).
The measured length (A) is to include MOUNTING GASKET and FLANGE, if used.
D) The burner may now be attached to the heating unit by insetting the AIR TUBE through the BURNER ACCESS
HOLE (8) and into the appliance, making sure the BOLTS (1) line up with the two HOLES (5) in the ADJUSTABLE
COLLAR (9). Secure the burner in place using two NUTS (7).
A visual verification of the air tube insertion into the combustion chamber of the heating unit is suggested. Dimension B
should be at least 1/4" (see drawing).
NOTE:
A suggested method for creating mounting bolt holes in the mounting gasket: Hold the gasket against the appliance
mounting bolts using the mounting flange for proper positioning. Lightly tap the flange with a hammer to form the holes.
METHOD 2 – SEMI-FLANGE COLLAR
A) Follow item C from METHOD 1.
B) Align the air tube and attached adjustable collar so air tube is centered in the burner access hole of the boiler/fur-
nace unit. Mark the center of the two holes in the ADJUSTABLE COLLAR on to the front plate of the heating unit.
Then drill 1/4" inch (6.5 mm) holes through the front plate of the unit, using marks as a guide.
C) Install two short BOLTS (1) through the front plate of the heating unit from the inside, and secure on the outside us-
ing the two special CHROME NUTS (2).
D) Follow item D from METHOD 1.
METHOD 3 – PEDESTAL MOUNT
Secure the MOUNTING FLANGE to MOUNTING PEDESTAL using the hardware provided with the pedestal. Secure
burner to MOUNTING FLANGE as in METHOD 1, item A, C and D.
NOTE:
It is suggested that the pedestal be anchored in position on the floor by installing brackets over the pedestal tube and
securing brackets to the floor.
WHEN THE COMBUSTION CHAMBER IS LINED WITH A REFRACTORY MATERIAL, IT IS
IMPERATIVE THAT THE END CONE NOT PROTRUDE INTO THE CHAMBER AREA, AS EXCESSIVE
HEAT AT BURNER SHUT DOWN WILL DAMAGE THE END CONE.
WARNING
4
2903222