TECHNICAL DATA

SPECIFICATIONS

Fuel
F3 Firing rate - Effective Output
F5 Firing rate - Effective Output
Voltage (single phase)
F3 Absorbed electrical power
F5 Absorbed electrical power
Motor (rated)
Capacitor
Pump pressure
Primary control
Ignition transformer

BURNER AND MOUNTING FLANGE DIMENSIONS

Model
A
Inches
8 15/32
9 59/64
F3
mm
215
Inches
9 11/64
10 11/16
F5
mm
233
E1: 10-inch long (254mm) tubes are also available.

BURNER COMPONENTS IDENTIFICATION

1
2
3
4
8
17
16
15
No. 2 Fuel Oil
0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h
0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h
120V 60Hz (+ 10% - 15%)
175 Watts
264 Watts
3250 rpm Run Current 2.2 AMP
12.5 Microfarads
130 to 200 psi
RIELLO 530 SE/C
8kV 16mA
B
C
D
6 15/32
3 1/2
252
164
89
7 3/32
3 1/2
272
180
89
9
10 11
E
F
6
8 29/32
152
226
6
9 13/32
152
239
7
6

BURNER COMPONENTS

5
1
Lockout indicator lamp and reset button
2
Primary control
3
Primary control sub-base
18
4
Pump pressure regulator
5
Motor
6
Air adjustment fixing screws
12
7
Capacitor
8
Combustion Head
13
9
Semi Flange
10
Turbulator adjustment screw
11
Air tube cover
12
Coil
13
Vacuum gauge port
14
Pressure gauge and bleeder port
14
15
Return fuel line port
16
Supply fuel line port
17
Mounting flange with gasket
D8799
2
B
E
F
E1
D7352
5 1 / 2 "-140mm
7 1 / 2 " - 190 mm
8 15 / 32 " - 215 mm
D7351
2903222

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

37261213726221