Figure 3-3
An example of fastening on the mounting bracket in the case of differential pressure and vertical differential
pressure lines
3.4
"Level" installation
3.4.1
Instructions for level installation
Requirements
Note
Compare the desired operating data with the data on the nameplate.
Please also refer to the information on the remote seal if this is fitted.
Note
Protect the transmitter from:
● Direct heat
● Rapid temperature changes
● Severe soiling
● Mechanical damage
● Direct sunlight
Note
Select the height of the mounting flange such that the pressure transmitter is always mounted below the lowest fill height to
be measured.
The installation location is to be as follows:
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-02, 12/2012
15