Lock release function active during the opening phase (with command
K, 9, Remote, P) - When the open command is given, motors M1 and
M2 perform a closing manoeuvre for a period of 1 second, at the same
time the electric lock release is activated. Motors M1 and M2 then stop
for 0.5 seconds, and restart to initiate the opening manoeuvre.
Lock release function active during the closing phase (with command K,
11, Remote control, Automatic closing) - When the close command is
given, motors M1 and M2 perform an opening manoeuvre for a period of
1 second, at the same time the electric lock is activated. Motors M1 and
M2 then stop for 0.5 seconds and start the closing manoeuvre.
FUNCtion 5 is only available if the plant is set-up as 1 or 2 leafs (FUNCtion A,
OPTion 2). The electric lock is active for 1.5 seconds at the start of each
opening/closing manoeuvre (if FUNCtion A OPTion 8 is active).
AUTOMATIC, JOGGING OR MANNED OPERATION
?
ESC
OPTION
enabled
ENTER
ESC
AUTOMATIC:
The remote control and buttons K and 9 are disabled if the automation is
already in the opening phase. If the automation is in the closing phase,
pressing the Remote control or buttons K and 9 will stop the automation
and automatically reinstate the opening phase after a pause of 2 seconds.
JOGGING:
Each time the commands K or Remote control are pressed, a jogging
manoeuvre is instigated with the sequence Open-Stop-Close-Stop-Open-
etc. Each time the command 9 is pressed, a jogging manoeuvre is
instigated with the sequence Open-Stop-Open. Each time the command 11
is pressed, a jogging manoeuvre is instigated with the sequence Close-
Stop-Close.
MANNED:
The command is only possible by pressing commands 9 and 11 and keeping
them pressed. The Remote control and commands K and P are disabled.
Automatic closing is disabled. The safety devices are enabled. The safety
devices stop the movement of the plant even if the operator keeps the
command button pressed.
FUNCTION TO ENABLE RELAY CARD 1 or 3 ALSO DURING CLOSING
This function can now also be activated during closing.
Operation mode and timer settings remain unchanged.
The time interval is repeated if transit past photocells occurs only during closing.
TIMER FUNCTION
This function is useful at peak times when traffic slows down (e.g. entry/exit of
employees, emergencies in residential zones or parking/waiting for removals).
APPLICATION
Connect a switch and/or daily/weekly type timer (in place of or in parallel to an
N.O. pushbutton 8-9) to enable barrier opening and keep the barrier open while
the switch is turned on or while the timer is activated.
All control functions are inhibited while the barrier is open.
When the switch is turned off, or when the set time has elapsed, controls are re-
enabled and barrier closing is possible.
If FUNCTION 2 OPTION 1 is enabled, the barrier closes automatically when
the switch is turned off or the set time has elapsed.
FUNCtion 6
OPTION
inhibited
ENTER
OTHER PROGRAMMABLE FUNCTIONS
The following functions are described in the instruction booklets supplied
separately with each optional product:
FUNCTION 7: AUXILIARY BOARD MANAGEMENT
FUNCTION 8: BOARD MANAGEMENT FOR TWO-SPEED MOTORS
FUNCTION 9: FUTURE FUNCTION
TECHNICAL CHARACTERISTICS AQM22 and AQM22-FE
- Temperature range
- Humidity
- Supply voltage
- Frequency
- Maximum consumption of card (excluding motors, lamps and external
actuators)
- Transient mains power drops
- Maximum power at motor output shaft
- Max. load at flasher output
- Available current at photocell power output
- Available current at photocell power output
- Av. current at Radio receiver and D+D-connector
- Weight of equipment
- Electrical protection
- Dimensions
- All inputs must be used as clean contacts because the power supply is
generated on the card and is arranged so as to ensure double or reinforced
insulation with respect to live parts.
- All inputs (function - safety) are controlled by a programmable integrated circuit
(PAL).
from 0 to 70°C
< 95% without condensation
230V~ ± 10%
50/60 Hz
50 mA - 60 ma
100 mS with tension at 40%
736W
40W
400 mA 24Vac
800 mA 24Vac
200 mA 12Vac
2,2 Kg - 2,7 Kg
IP 55
33 x 24,2 x 12,4 cm