pag. 16 di 24
2nd Pulse: stops counting the manoeuvring time of the first leaf M1 and opens
the second leaf M2 while starting a new count.
3rd Pulse: stops counting the manoeuvring time of the second leaf M2 and
starts counting the delay time prior to automatic closing.
- Allow the required delay time to pass with the gate open (maximum 15
minutes, after which the gate will close automatically).
4th Pulse: stops counting the delay time and starts closing the second leaf M2
(NB: the delay time will only function if FUNCtion 2 OPTion 1 - automatic
closing delay time - is or will be activated).
- Allow the required time lag between the closing manoeuvre of each leaf to
pass before the next pulse.
5th Pulse: starts closing the first leaf M1 (determines the closing time-lag
between the leafs).
SYSTEM WITH 1 MOTOR AND NO LIMIT SWITCH DETECTION
procedure to follow starting with the gate closed position
To start the timing, press one of the K/9/turn/Remote control buttons.
1st Pulse: gate opening control pulse and open time counter start
2nd Pulse: stops counting the manoeuvring time of the gate and starts counting
the delay time before automatically closing the gate.
- Allow the required delay time to pass for the gate to remain open (maximum
15 minutes, after which the gate will close automatically).
3rd Pulse: stops the count and starts the closing manoeuvre of the gate (NB
the delay time will only function if FUNCtion 2 OPTion 1 - automatic closing
delay time - is or will be activated)
SYSTEM WITH 2 MOTORS AND LIMIT SWITCH DETECTORS
procedure to follow starting with the gate in the closed position
To start the timing, press one of the K/9/turn/Remote control buttons.
1st Pulse: opens the first leaf M1, memorising the opening time until the open
limit switch is reached
- limit switch contact (4) will stop the first leaf M1 manoeuvring time counter and
will start manoeuvring the second leaf M2, starting a new count of the
manoeuvring time.
- limit switch contact (12) of the second leaf opening will stop the counter of the
second leaf M2 manoeuvring time and start counting the delay time prior to
automatic closing
- allow the required delay time to pass for the gate to remain open (maximum
15 minutes, after which the gate will close automatically).
2nd Pulse: stops counting the delay time prior to automatic closing and starts
the closing manoeuvre of the second leaf M2 (the delay time will only
function if FUNCtion 2 OPTion 1 - automatic closing delay time - is or will
be activated)
3rd Pulse: starts the closing manoeuvre of the first leaf M1 (thus determining
the time lag between the closing manoeuvres of the two leafs)
NOTE: If the gate is configured for two sliding leafs, the time lag function will
not be activated.
SYSTEM WITH 1 MOTOR AND LIMIT SWITCH DETECTORS
procedure to follow starting with the gate in the closed position
To start the timing, press one of the K/9/turn/Remote control buttons.
1st Pulse: opens the gate and activates the gate opening time
- open limit switch contact (4) stops the gate opening manoeuvre time and
starts the delay time count prior to automatic closing
- allow the required delay time to pass for the gate to remain open before
automatic closing (maximum 15 minutes, after which the gate will close
automatically).
2nd Pulse: stops counting the delay time prior to automatic closing and starts
the closing manoeuvre (the delay time will only function if FUNCtion 2
OPTion 1 - automatic closing delay time - is or will be activated)
OPT 2 - PEDESTRIAN TIME ADJUSTMENT
procedure to follow starting with the gate closed
Programming procedure:
ENTER
To start the time counter, press button P (Pedestrian function).
1st Pulse: opens the first leaf and activates the manoeuvring time counter
(maximum 20 seconds)
2nd Pulse: stops the first leaf M1, memorises the opening time and starts the
delay time count prior to automatic closing of the leaf (the delay time will
only function if FUNCtion 2 OPTion 4 - automatic pedestrian closing time -
is or will be activated)
- allow the required delay time for the gate to remain open to pass (maximum 1
minute, after which the leaf will close automatically).
3rd Pulse: stops and memorises the waiting time for automatic closing and
activates the closing manoeuvre.
Note: during normal operation, the gate will not open fully until the
"pedestrian leaf" is closed.
OPT 3 MANOEUVRING TIME ADJUSTMENT
first leaf M1 and second leaf M2 together
procedure to follow starting with the gate closed
Programming procedure:
ENTER
OPT 4 Automatic closing delay time adjustment
procedure to follow starting with the gate closed
ENTER
OPT 5 Second leaf closing delay time adjustment
procedure to follow starting with the gate closed
ENTER
the time lag between the two leafs is fixed at 2 seconds.
OPT 6 Pedestrian opening time adjustment
procedure to follow starting with the gate closed
ENTER
OPT 7 Delay time adjustment
for automatic closing of pedestrian passage P
procedure to follow starting with the gate closed
ENTER
(max. ±9 seconds )
to confirm regulated time
setting
ENTER
(max. ± 9 seconds)
Follow the above procedure to select
and confirm the delay time in seconds
(max. ± 9 seconds)
Follow the above procedure to select
and confirm the delay time in seconds
N.B.: During the opening manoeuvre,
(max. ±9 seconds)
Follow the above procedure to select
and confirm the time in seconds
(max. ±9 seconds)
Follow the above procedure to select
and confirm the delay time in seconds