Setting The Boiler Parameters - Baxi 45 HTE Notice D'emploi Destinée À L'usager Et À L'installateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

14. setting the boiler parameters

The boiler parameters may only be modified by professionally qualified staff proceeding as follows:
a) press the
, keys on the boiler's front panel together for about 3 s until the parameter H90 appears on
the display;
b) press the
keys to select the parameter for modification;
c) press the
and
keys to modify the parameter;
d) press the
key to ex­it the programming function.
The following are the parameters generally used:
parameter n.
Description
H90
minimum D.H.W. temperature setting (°C).
H91
D.H.W. activation program
(0=active; 1=not active)
H505
maximum temperature (°C) of the central heating circuit HC1 corresponding to:
- the main circuit in systems with just one zone;
- the circuit of the zone where the QAA73 room temperature control device is installed in case
of systems with more than one high-temperature zone;
- the high temperature zone circuit in mixed systems and if the SIemenS Agu2.500 accessory
is used.
H507
maximum temperature (°C) of the central heating circuit HC2 of a system with more than one zone,
corresponding to the circuit of the low-temperature zone if the SIemenS Agu2.500 accessory
is used.
H516
Automatic Summer / Winter switching temperature (°C).
H532
Selection of temperature curve of central heating circuit HC1 (see graph 1)
H533
Selection of temperature curve of central heating circuit HC2 (see graph 1)
H608
pWm (%) Setting: Ignition load
H611
Speed setting (rpm) : Ignition load
H609
pWm Setting (%) : minimum power
H541-H610
pWm Setting (%) : maximum power Central heating / Domestic hot water
H612
Speed setting (rpm) : minimum power
H536-H613
Speed setting (rpm) : maximum power Central heating / Domestic hot water
H544
pump post-circulation time in central heating mode (min)
H545
Burner operating pause time between two start-ups (s)
H552
Hydraulic system setting (see instructions provided with the SIemenS Agu2.500 accessory)
H552 = 50 with Agu2.500 and with QAA73 + zones with room thermostat
H552 = 80 with rVA 47
H553
Configuration of heating circuits
H553 = 12 with Agu2.500
H615
programmable function:
Configuration of system with supplementary pump
H632 = 00001111 with Agu2.500 and with QAA73 + zones with room thermostat
H632 = 00001111 with rVA 47
H632
the value of Bit could be 1 or 0.
press the keys 5 and 6 to select the bit to modify (b0 is the bit on the right, b7 is the last bit on
the left).
to modify the Bit value press on the keys 7 and 8
H641
Fan overrun time setting (s)
Setpoint of autonomous AntIlegIonellA function
H657
60...80 °C = setting temperature range
0 = function inactive
IstructIons pErtaInIng to thE InstallEr
69
Factory setting
10
1
80
80
20
15
15
See
table 2
3
180
2
21
9
00001100
10
0
912.359.1 - IE

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

65 hte85 hte100 hte120 hte150 hte

Table des Matières