Configuring the Nordmann AT4 D for the operation with the external steam
bath control
40
7. If the contrast of the display is too strong or too weak, it can adjusted
using the potentiometer on the control board of the steam bath control.
This must be done before the touch panel is assembled.
Note: Detailed information on the operation of the control software of the
Nordmann AT4 D can be found in the operating instructions of the Nord-
mann AT4 D.
Setting the Modbus communication parameters
In the Modbus submenu "Remote" set the parameters as follows (Path: Main
Menu > User > Password entry: 3562 > Modbus > Remote):
Remote Sett:
Remote
Modbus Addr.:
1
Baudrate:
9600
Parity:
Even
Remote
Remote Sett :Remote
Modbus Addr.:1
Baudrate
:9600
Parity
:Even
Esc
Set
Set the operating mode
In the main menu set the parameter "Operat.Mode" to "Manual" (Path:
Main Menu > Operat.Mode):
Main Menu
Setpoint
:48°C
Operat.Mode :Manual
Duration
:45min
Fragrance
:Set
Light-2
:Off
Esc
Set
Setting the control mode
In the steam bath sub menu set the parameter "Operation" to "Panel" (Path:
Main Menu > User > Password entry: 3562 > Settings > BathSettings):
BathSettings
Operation
:Panel
Fan
:Set
Fragrance
:Set
Light
:Set
Temp.Sensor :Set
Esc
Set