4.3

Choosing location

4.4

Mounting the unit

4.4.1

Steam bath control for in-wall mounting

34
Please observe the following notes for the correct positioning of the external
steam bath control Nordmann TP:
The unit must not be installed in hazardous locations and in rooms where
water splashes may occur.
Do not mount the unit inside the steam bath cabin.
If possible mount unit at eye level.
Do not mount the unit in exposed places.
Do not mount the unit on vibrating components.
Continuous direct sunlight is harmful for the unit and can affect its correct
function. Therefore do not expose the unit to continuous direct sunlight.
CAUTION!
The electronic components of the steam bath control are very sensitive
to electrostatic discharge. For all installation work appropriate measures
must be taken to protect these components against damage caused by
electrostatic discharge (ESD protection).
1. At the desired location, mark mounting opening with the help of the
mounting template supplied and a spirit level, then ream out the mount-
ing opening.
1 9
T
Cavity wall
Tmin: 15 mm
Tmax: 53 mm
0 m
m
Massive wall
Tmin: 58 mm
1 9
0 m
m
T