WIKA TR10-0 Mode D'emploi page 18

Masquer les pouces Voir aussi pour TR10-0:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8. Safety-related instructions
Solid-machined
thermowell
(minimum wall thickness 1 mm)
EN
Legend:
 Connection head
 Neck tube
 Connection to thermowell
 Measuring insert
Temperature class classification, ambient temperatures
A heating in the connection head can occur with built-in transmitter through faulty
electronics. The permissible ambient temperatures depend on the housings used and any
additionally-fitted head-mounted transmitter.
For all WIKA connection heads with built-in WIKA temperature transmitters, the
following interrelation is valid:
The temperature increase on the surface of the connection head or housing is less than
25 K if the following conditions are observed: power supply U
transmitter is operated in a current limit of 22.5 mA.
This yields the following temperature class classification:
Atmosphere
Gas atmosphere
Dust atmosphere
The temperature class is dependent upon the user application and the ambient temperature.
18
Protection tube
(minimum wall thickness 1 mm)
 Process connection
 Terminal block/transmitter
 Flame path fitting
Temperature class
T6
T5
T4
T85 °C
WIKA operating instructions models TR10-0, TC10-0 (Ex d)
Without thermowell
maximum DC 30 V when the
B
Limits for ambient temperature
-20 ... +60 °C
-20 ... +75 °C
-20 ... +80 °C
-20 ... +60 °C
Welded bushing
welded

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tc10-0

Table des Matières