Inputs And Outputs; Programming The Parameters - Aprimatic Slide 230 Instructions D'installation, D'utilisation Et D'entretien

Platine de commande pour l'automatisation de portails coulissants 230 v
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.2

Inputs and outputs

(using button with N.O. contact or remote control)
START
- starts the automation (opening or closing) on the basis
of the current state and the operating logic settings.
(button with N.C. contact) - the input stops the wing
STOP
immediately. A START pulse is required to continue move-
ment. The STOP input has priority over all other functions
at all times.
- these photocells are only enabled
Closing photocells
on the closing stroke. When triggered, they will stop the
automation to close and then the automation reopens.
These photocells will prevent closing as long as they
are covered.
Auxiliary safety edge operating on opening stroke
this is a safety input enabled during the opening and clo-
sing stroke. When the safety edge is triggered during the
stroke, the rod will reverse for 2 sec. then will stop. With a
START, the movement will restart in the inversed direction.
Auxiliary safety photocells
obstacles on the opening and closing strokes; when trigge-
red on, they will stop the automation. When the photocells
are uncovered, after 1 sec. of pause, the movement will
restart in the original direction.
To signal the status of the automation:
Warning light (remote signal):
AUTOMATION STATUS
FLASHING LIGHT
gate opening
fl ashing (1 sec.)
gate closing
fl ashing (1 sec.)
gate open
light OFF (parameter
gate closed/stopped light OFF
auxiliary safety
light ON
routine maintenance fl ashing (0.5 sec.)
• Auxiliary output using external relay depending on
ae
(
) parameter: 2 sec pulse type with activation by remote
ch1
4
control (
-
) (ex: pedestrian gate electric lock actuation)
OR timer (ex: lighting).
Courtesy light - light ON when START or PEDESTRIAN
START is pressed, with programmable timer (
4.3
Checks and warnings on display
Press once brief the
YELLOW : the displays switch ON. To
switch them OFF, press once brief the YELLOW again (
5.

PROGRAMMING THE PARAMETERS

IMPORTANT! The gate must be stopped and closed before you can start programming.
WARNING: All input signals will be ignored during programming.
Press and hold RED button
Release the RED button
BLUE
RED when a parameter shown
pressing the BLUE button
Press and hold the RED button for 3 seconds
The parameter has now been modifi ed. More modifi cations can be made before you exit the programming function.
WARNING: modifi cations are only confi rmed when you exit the programming function (display switched OFF).
If the power supply fails for any reason during programming, all the modifi cations you have made will be lost.
To EXIT programming:
Parameters enabling RESET or operations involving MEMORIES: before the modifi cation is confi rmed the display shows
if confi rmation is given (RED button)
SLIDE 230
- these photocells detect
Flashing light /
WARNING LIGHT
light ON
fl ashing
AH
) light ON
light OFF
-
-
ae
).
fi g.6).
to select a new value
Release the RED button
YELLOW
fl ashes for 3 sec.
fi g. 6 -
Checks and warnings on display
1
8 8 8 8
display 1: GATE STATUS
C
= CLOSED
b
= OPENING
A
= OPEN
d
= CLOSING
E
= LOCKED
0
= OBSTACLE detection
display 2: INPUTS (ON=contact closed)
8
-
1 = START radio
2
2 = CLOSING PHOTOCELL
1
4 = PEDESTRIAN START
7
5 = SAFETY DEVICE during OPENING
6
4
6 = START
5
7 = STOP
8
display 3: LIMIT SWITCHES
1
(OFF=the limit switch is triggered)
1 = OPENING limit switch
6
6 = CLOSING limit switch
8
display 4: OUTPUTS
1
3
(ON=output active)
1 = FLASHING LIGHT
3 = WARNING LIGHT
ERROR CODES
NoEE
= failed access to Memory during the power up ;
I nit
= missing of data in memory (press YELLOW and
BLUE simultaneously for approx. 3 sec.
appears on display press START) ;
Er1
= failed access to the memory during
Er2
= closing photocell test;
Er3
= auxiliary photocell test;
Er5
= missing the encoder at start-up (for solution
Er9
= motor/limit switches (verify the connections) ;
ErFc
= stop due to a failure of limit switches/encoder ;
EreNc
= no communication control unit / encoder ;
MAn
= routine maintenance is required (fl ashes for
3 sec. during the programming access).
PROC
the display shows
displays the fi rst parameter with the value set
scrolls through the parameters
shows the value set (marked by the bullet)
scrolls through the values
3 fl ashes confi rm the modifi cation
the new setting is displayed
returns to the parameters
press the YELLOW button until the display is switched OFF
donE
Er
(positive outcome) o
- 23 -
CONTROL UNIT
2
3
4
UPLOAD
LO
+ error code in the event of failure.
Lrn
/
;
DOWNLOAD
par.3);
0
.
SURE
,