Instructions for installation and use
2.2. Safety information for the installer
● Installation may only be performed by a qualifi ed electrician or
similarly qualifi ed person.
● Work on the sauna control unit may only be performed when the
power has been disconnected.
● A three-phase shut-off device with a 3 mm contact opening must
be provided during installation. This is provided by the fuse.
● The sauna control unit must be installed outside the sauna room
at a height of approx. 1.70 m or in accordance with the recom-
mendation issued by the sauna manufacturer. The ambient
temperature must be within a range spanning -10 °C to +40 °C.
● The heater sensor must be attached in a way that it is not af-
fected by a fl ow of air.
● The heater supply cable must have a minimum cross-section of
2.5 mm
2
and be temperature resistant up to 150 °C.
● Also comply with the regulations applicable at the installation
location.
● For your own safety, consult your supplier in the event of prob-
lems that are not explained in suffi cient detail in the installation
instructions.