11. Function
Triggering water flow
11.1 Press the button.
• Water flows.
• Water flow stops automatically after a set flow duration.
☞
The flow duration can be set in the range 1 – 15s.
Selecting the temperature
locked
swivelling
12. Thermal Disinfection
This shower fitting provides the features necessary to perform thermal disinfection to
reduce the risk of Legionella infection.
Thermal disinfection is triggered by overturning the thermostat.
Warning!
Protective measures for persons (scald-protection) must be provided during thermal
disinfection, e.g. closing off sanitary rooms.
Failure to observe can cause bodily harm due to scalding.
The operator is responsible for performing, monitoring and logged (room, tap, date,
time, temperature, duration).
Any liability claims by third parties attributed to the operator improperly performing
thermal disinfection are therefore declined by the manufacturer.
The thermostatic fitting has been prepared for performing thermal disinfection by
overturning the thermostat. By unlocking the concealed stop on the temperature
selector lever, manual thermal disinfection can be performed on the thermostatic
fitting (flushing with a water temperature ≥ 70°C).
Caution!
Do not touch the housing during the thermal disinfection process.
Failure to observe can cause bodily harm due to scalding.
12.1 With the Allen key depressed, turn the temperature selector handle (a) counter-
clockwise until it reaches the stop.
12.2 When the stop is reached, pull out the Allen key and continue to turn the temper-
ature selector handle (a) over the stop.
12.3 Turn the temperature selector handle (a) counter-clockwise until it reaches the stop
(end position).
12.4 Trigger the valve.
12.5 Measure the hot water temperature.