Sigfox DELTA P - Guide utilisateur / User guide version V2.0.1
In order to ensure proper connection of the product, take care to
connect the tube positioned where the pressure is highest on the
P+ support (indicated on the base plate) and to connect the tube
going into the section with the lowest pressure on the P- support.
5 mm inside diameter tubes (not
supplied)
4.4. Cabling Digital inputs/outputs 2 via the terminal block
In order to be able to couple a 0 -10 V sensor or dry contact sensors with the product, connect the sensor to the board terminal block.
Connecting the wires:
1. Open the case (paragraph 5.1)
2. Connect the wires as shown in the diagram below
3. Configure the registers associated with the connected sensors (paragraph 3)
4. Close the case
5. Restart the product with the magnet as for the initial start-up.
6
5
4
3
2
1
After this procedure, product will react as if it were the initial start-up
Examples :
Sigfox DELTA P may easily be coupled with a newer ventilation system with dry contact outputs. It may also be coupled with a current clamp to
monitor the voltage in the power cable of the ventilation system on which it is positioned and thus more readily detect a power failure.
P+
P-
6
GND
5
0-10 V
4
GND
TOR2
3
GND
2
1
TOR1
In order to avoid premature degradation of tubes
exposed to the sun, Adeunis strongly recommends
covering the tubes with an anti-UV sheath.
EN
Page
49