6.3.3
Commissioning steps
)
Note!
The following can be connected to the X70 diagnostic interface:
ƒ
ƒ
Only some parameters must be adapted for the drive. Then the drive application
can be controlled immediately in the preset "Terminals 0" control mode via the
digital and analog inputs. Alternatively, the keypad can be used for defining the
required setpoints and control signals in the "Keypad" control mode.
How to proceed:
1. Wiring of power terminals
–
Make use of the mounting instructions supplied with the inverter to
wire the power terminals according to the requirements of your device.
2. Wiring of control terminals.
–
The preconfigured I/O connection can be changed via configuration
parameters. See chapter "User−defined terminal assignment".
–
Assignment in the preset "Terminals 0" control mode:
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0
Commissioning via the diagnosis terminal
USB diagnostic adapter (E94AZCUS)
X400 diagnosis terminal (EZAEBK200x)
– The functions of the X400 diagnosis terminal and keypad
(EZAEBK100x) are identical.
l
Commissioning
Commissioning steps
6