5
Settings
(
Stop!
Automatic motor start
In "Local mode" The auto−start option "Inhibit at power−on" is not
set. When the mains is connected, the motor starts if the controller
enable RFR is bridged or set.
("Local mode" => DIP1/1 = ON and DIP2/5−7 = OFF)
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
ƒ
For initial commissioning, settings can be made via DIP switch and
potentiometer. The settings must be made before mounting the drive unit since
the setting elements cannot be accessed from the outside.
From software version 07.00.00 onwards, you can use DIP2/8 to set two
different pre−assignments of DIP1, DIP2, P1, P2, and P3:
DIP2/8 = OFF: DIP switch/ potentiometer assignment 0
ƒ
DIP2/8 = ON: DIP switch/ potentiometer assignment 1
ƒ
Up to software version 07.00.00, only DIP switch/ potentiometer assignment 0
is available.
From software version 08.00.00 onwards and when using a POWERLINK
communication module, you can influence the IP address setting with DIP1/1:
DIP1/1 = OFF: DIP1/2 ... DIP1/8, P1, P2 and P3 are inactive, DIP2 serves to
ƒ
set the IP addresses for POWERLINK
DIP1/1 = ON: DIP switch function and potentiometer assignment as
ƒ
described, IP address setting from code C13899
Detailed information can be found in the POWERLINK (EDS84DMOTPL)
communication manual.
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0
Danger or damages through unexpected motor start.
Decouple the motor from the drive train during commissioning
phase.
Replace the factory−set bridge at RFR by an NO contact.
Do not set controller enable.
l
Settings
5
77