4.3
Measures when drive is used in IT systems
If the drive is mounted within an IT system, internal filters must be separated
from the PE conductor.
How to proceed:
1. If the controller has already been mounted: switch off mains voltage!
2. Make IT screw accessible.
–
Devices up to 3 kW: unscrew small cap on the top.
–
Devices from 4 kW: remove small cover on the top.
3. Unscrew and remove the screw(s).
4. Screw the cap on or fit the cover.
0.37 ... 3 kW
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0
Mechanical installation
Measures when drive is used in IT systems
l
4