Commissioning

7
Commissioning
Preconditions for initial switch−on
The wiring unit is mounted and wired according to the instructions,
ƒ
directly on a motor clamping flange or
with the wall adapter on a suitable surface near the motor.
Connections with the mains, motor, holding brakes, etc. have been
ƒ
established.
The communication unit has been mounted and wired according to the
ƒ
scheduled application.
Input and output signals
Safe input
Fieldbus
(depending on the version, only available optionally)
If required, the basic settings for "local mode" have been carried out.
ƒ
DIP switches
Potentiometer
The drive unit has been mounted and screwed together.
ƒ
Use available control functions reasonably, e.g.
ƒ
Inhibit controller enable
Set speed adjustment to the minimum setting
Activate safety system
The use of a brake resistor has been checked.
ƒ
In the case of dynamic loads or difficult control conditions, the use of the
internal brake resistor E84DZEW47R0 is always recommended for the
devices E84DGDVB4024 ... 7524 (4 ... 7.5 kW).
}
Danger!
High hazard potential during commissioning
Incorrect settings may cause unexpected and dangerous motor and
system movements.
Possible consequences:
ƒ
ƒ
Protective measures:
ƒ
ƒ
62
Damage to material assets
Injury to persons
Clear hazardous area
Observe safety instructions and safety clearances
l
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 6.1