6
Commissioning
Commissioning via the diagnosis terminal
6.3
Commissioning via the diagnosis terminal
The X400 diagnosis terminal serves to quickly and easily set parameters and
display current actual values and device states by means of the corresponding
display parameters. For this purpose, the diagnosis terminal must be plugged
onto the X70 diagnostic interface on the top of the device.
}
Danger!
Uncontrolled motor movement possible
In general, changing a parameter causes an immediate response in
the inverter.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
)
Note!
Plugging and unplugging the diagnosis terminal during operation is
permissible.
,
More information ....
Detailed information regarding the diagnosis terminal can be found
in the operating instructions for the X400 keypad & diagnosis
terminal.
94
This may lead to undesirable behaviour on the motor shaft if the
inverter has been enabled.
Make changes in small steps and wait for response.
Certain device commands or settings which may cause critical
states of drive behaviour constitute exceptions. Such parameter
changes are only possible if the inverter is inhibited. Otherwise, a
corresponding error message will be issued.
l
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0