Protection of persons and equipment
Enclosure
(Earth) leakage
current
Total fault current
Motor mounting
Wall mounting and
Lenze system cable
£ 3 m
Wall mounting and
Lenze system cable
> 3 m
Additional
equipotential bonding
Protective insulation
of control circuits
Insulation resistance
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 9−0
General data and operating conditions
Seal unused bore holes for cable glands by means
l
of blanking plugs!
Seal unused connectors by means of protection
l
covers or blanking plugs!
EN 60529
8400 motec Set
Wall mounting
without switch
Wall mounting with
service switch / with
service switch and
control elements
Wall mounting with
service switch and
protective function
NEMA 250
8400 motec Set
Wall mounting
without switch
0.37 ... 3.0 kW
4.0 ... 7.5 kW
Wall mounting with
switch
0.37 ... 3.0 kW
EN 61800−5−1
> 3.5 mA AC,
> 10 mA DC
In TN systems the following earth−leakage circuit
breakers can be used:
0.37 ... 3.0 kW
4.0 ... 7.5 kW,
f
= 8/16 kHz
ch
4.0 ... 7.5 kW,
f
= 4 kHz
ch
0.37 ... 3.0 kW
4.0 ... 7.5 kW,
f
= 8/16 kHz
ch
4.0 ... 7.5 kW,
f
= 4 kHz
ch
0.37 ... 7.5 kW
M5 thread with terminal in the WU for connection of
a 16 mm
EN 61800−5−1
Safe isolation from mains by double (reinforced)
insulation
EN 61800−5−1
<2000 m amsl: overvoltage category III
>2000 m amsl: overvoltage category II
l
Technical data
IP65
IP54
IP64
Type 4X (interior)
Type 12
Type 4X (interior)
Type 12
Observe the regulations and
safety instructions!
30 mA, type B
30 mA, type B
300 mA, type B
30 mA, type B
30 mA, type B
300 mA, type B
300 mA, type B
2
PE cable
3
67