Briggs & Stratton 071048 Guide D'installation Et D'utilisation page 19

100/200 a commutateur de transfert automatique avec disjoncteur de l'alimentation symphony ii
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

50 Amp Model
F
G
A - Priority Selector
B - 50 Amp Relay
C - Relay Status LED
D - Signal Communication LED
E - Neutral Connection
F - Load Connection
G - Power/Line Connection
LED's are for signal communication status and relay position
status.
Utility power present:
• Normal State
Relay Position Status LED (C)
-
Green LED - Relay is closed; power available to
appliance/load
Signal Communication Status LED (D)
-
Orange LED - No communication and appliances/
loads cannot be managed by Symphony II System
• Problem State (see Troubleshooting)
Relay Position Status LED (C)
-
No LED - Power not available to managed
appliance/load; 5 minute delay has not expired,
verify correct wiring
-
Red LED - 50 Amp relay contacts in incorrect state;
replace 50 Amp module
Signal Communication Status LED (D)
-
No LED - No power to 50 Amp control board; verify
correct wiring
-
Green LED - Broken LED; replace 50 Amp module
-
Red LED - Fault in system; verify current
transformer connections, verify terminations on
orange and yellow communication wires
A
B
C
D
E
Generator power present:
• Normal State
Relay Position Status LED (C)
-
Green LED - Relay is closed; power available to
appliance/load
-
No LED - Relay open, no power, Symphony II is
managing load
Signal Communication Status LED (D)
-
Green LED - Signal communication detected and
appliances/loads are being managed after 5 minute
delay
• Problem State (see Troubleshooting)
Relay Position Status LED (C)
-
No LED - Power not available to managed
appliance/load; 5 minute delay has not expired,
verify correct wiring
-
Red LED - 50 Amp relay contacts in incorrect state;
replace 50 Amp module
Signal Communication Status LED (D)
-
No LED - No power to 50 Amp control board; verify
correct wiring
-
Orange LED - Signal communication not detected;
verify correct wiring
-
Red LED - Fault in system; verify current
transformer connections, verify terminations on
orange and yellow communication wires
19

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

071054071049