P.11 ... P.18 – Function of output relays 1 ... 8:
OFF = Not used.
1 .. 32 = Weight of the step. This relay drives a bank of cpacitors which power is n times (n = 1...32) the smallest power defined with parameter P.06.
ON = Always on.
NOA = Alarm normally de-energised. The relay is energised when any alarm with the Global alarm property arises.
NCA = Alarm normally energised. The relay is de-energised when any alarm with the Global alarm property arises.
FAN = The relay controls the cooling fan.
MAN = Relay is energised when device is in MAN mode.
AUT = Relay is energised when device is in AUT mode.
A01 ... A13 = The relay is energised when the specified alarm is active.
P.19 – Setpoint (target value) of the cosphi. Used for standard applications.
P.20 – Language of scrolling alarm messages.
ADVANCED MENU
CODE
DESCRIPTION
P.21
Password enable
P.22
User password
P.23
Advanced password
P.24
Wiring type
P.25
Step trimming
P.26
Setpoint clearance +
P.27
Setpoint clearance -
P.28
Step insertion mode
P.29
Cogeneration cosϕ setpoint
P.30
Disconnection sensitivity
P.31
Step disconnection passing in MAN
P.32
Capacitor current overload alarm threshold
P.33
Capacitor overload immediate disconnection threshold
P.34
VT primary
P.35
VT secondary
P.36
Temperature unit of measure
P.37
Fan start temperature
P.38
Fan stop temperature
P.39
Temperature alarm threshold
P.40
Step failure alarm threshold
P.41
Maximum voltage alarm threshold
P.42
Minimum voltage alarm threshold
P.43
THD V alarm threshold
P.44
THD I alarm threshold
P.45
Hours maintenance interval
P.46
Bar-graph function
P.47
Default auxiliary measure
P.48
Backlight flashing on alarm
P.49
Serial node address
P.50
Serial speed
P.51
Data format
P.52
Stop bits
P.53
Protocol
8
ACC
UoM
DEF
RANGE
Adv
OFF
Usr
001
0-999
Adv
002
0-999
Usr
3PH
3PH three-phase
1PH single-phase
Usr
OFF
ON Enabled
OFF Disabled
Usr
0.00
0 – 0.10
Usr
0.00
0 – 0.10
Usr
STD
STD Standard
Lin Linear
Usr
OFF
OFF /
0.50 IND – 0.50 CAP
Usr
sec
OFF
OFF / 1 – 600
Usr
OFF
OFF Disabled
ON Enabled
Adv
%
125
OFF / 100...150
Adv
%
150
OFF / 100.. 200
Usr
V
OFF
OFF / 50-50000
Usr
V
100
50-500
Usr
°C
°C °Celsius
°F °Fahrenheit
Adv
°
55
0...212
Adv
°
50
0...212
Adv
°
60
0...212
Adv
%
OFF
OFF / 25...100
Adv
%
120
OFF / 90...150
Adv
%
OFF
OFF / 60..110
Adv
%
OFF
OFF / 1..250
Adv
%
OFF
OFF / 1..250
Adv
h
9000
OFF/1...30000
Usr
Kvar
Kvar ins/tot
ins/tot
Corr att/nom
Delta kvar att/tot
Usr
Delta
Deltakvar
kvar
Week TPF
Cap. Current
Temp
THDV
Usr
OFF
Usr
01
01-255
Usr
bps
9.6k
19.2k
38.4k
Usr
8 bit – n
8 bit, no parity
8 bit, odd
8 bit, even
7 bit, odd
7 bit, even
Usr
1
Usr
Modbus
Modbus RTU
RTU
Modbus ASCII
Modbus TCP
G
B
OFF
ON
V
A
THDI
ROT
OFF
ON
1.2k
2.4k
4.8k
9.6k
1-2